CAN/ULC-S561

CAN/ULC-S561 is the Canadian standard for the installation and services of fire signal receiving centres and systems, which is the monitoring side of the job: the transmitter at the building, the communication path, and the central station that receives the signal and calls the fire department. In Ontario the Building Code brings it in at Article 3.2.4.7, which requires notification of the fire department in conformance with S561, and Fire Code Article 6.3.1.2 puts the ongoing duty on the building owner, including holding written documentation from the operator that the service complies. The current published edition is CAN/ULC-561-2024, the 3rd edition, first published 1 June 2020 and revised 22 July 2024. Ontario designates neither: Building Code Table 1.3.1.2 and Fire Code Table 1.2.1.A both name S561-13, the 2013 edition.

What CAN/ULC-S561 covers

Monitoring, end to end, as a service rather than as a box. It covers the installation of the transmitting equipment at the protected building, the communication channels back to the receiving centre, the operation of that centre, and the records and documentation the service has to produce. It is a services standard, which is why the Fire Code asks the owner for paperwork from the operator rather than for a device.

The triggers in Ontario are worth memorising, because they catch nearly every building anyone argues about. A single stage system in a Group A occupancy over 300 occupants or in a retirement home. Any system that includes waterflow indicating devices, which is every sprinklered building with a flow switch. And any two stage system. The full set with the code text behind it is in fire alarm monitoring in Canada.

What it does not cover

S561 is not the equipment standard. The receiving centre equipment itself is listed to CAN/ULC-S559, a different document, and confusing the two is the most common error in monitoring specifications. S561 also does not cover the fire alarm system inside the building, which is S524 to install and S536 to inspect, and it does not decide whether a building needs monitoring at all. That decision is a building code decision.

Being monitored does not reduce anything else you owe. The annual inspection still happens. The verification still happens.

What brings it into force in Ontario

Building Code Division B Article 3.2.4.7 requires that notification of the fire department be provided in conformance with CAN/ULC-S561 where the code calls for it. That is the construction end. Fire Code Article 6.3.1.2 is the operating end: the owner must keep the monitoring in service and must hold written documentation from the central station operator confirming that the service complies with the standard. If you are a technician handing a building over, that document is a deliverable, and owners frequently do not have it. The owner side is set out in fire alarm compliance for building owners.

Published edition versus the edition Ontario designates

The current published edition is CAN/ULC-561-2024, the 3rd edition, first published 1 June 2020 and revised 22 July 2024, sold with the "S" dropped from the designation. Both Ontario codes designate S561-13, the 2013 edition, so the gap here is a full generation of the standard rather than a revision. A monitoring company quoting compliance with the current edition is describing what it sells, not what your permit is assessed against. The dated comparison across the family is in the edition tracker, and the practical rule is unchanged: read the referenced documents table, not the article, and not the supplier's brochure.

Who uses it, and when

The alarm contractor, when the communicator or transmitter is installed and programmed. The monitoring company, continuously, because most of the standard is about how the receiving centre operates. The building owner, who signs the monitoring contract and has to produce the compliance letter on request. The inspector, who asks for that letter and for evidence that the signal path is supervised.

The standards it gets confused with

S559 for the receiving centre equipment. S524 for the fire alarm installation the transmitter is connected to. And any American central station standard, which is not the basis of a Canadian requirement.


Fire Alarm Academy provides educational content only. It does not confer any certification, licence or credential, and it is not affiliated with, endorsed by, or accredited by the Canadian Fire Alarm Association, the Electrical Contractors Association of Ontario, ULC Standards, UL Standards and Engagement, CSA Group, the Electrical Safety Authority, any authority having jurisdiction, or any manufacturer. Always work from the edition of any standard adopted by your authority having jurisdiction.

Sources

Related terms

Fire Alarm Academy

Canadian fire alarm training built on CAN/ULC standards and the Ontario codes, taught by a licensed 309A electrician who does the work.

Learn

Free Resources

Company

Disclaimer: Fire Alarm Academy is an educational course. It is not a certification, licence, or accredited program, and it is not affiliated with or endorsed by the Canadian Fire Alarm Association, ECAO, ULC Standards, or any authority having jurisdiction. Course content does not replace the CAN/ULC standards, the Canadian Electrical Code, the applicable building or fire code, manufacturer instructions, or the direction of your AHJ. Always verify against the edition adopted in your jurisdiction.

© 2026 Fire Alarm Academy. Built for the trade.