Fault tolerance / the single-fault rule

The principle in the 2019 edition of S524 that where a circuit serves more than one NBC-required fire alarm zone, a single fault — open, short or ground — must not prevent normal operation of field devices in more than one zone. It applies to all circuits leaving the control unit.

Read more: The four Canadian fire alarm standards explained

Fire Alarm Academy

Canadian fire alarm training built on CAN/ULC standards and the Ontario codes — taught by a licensed 309A electrician who does the work.

Learn

Free Resources

Company

Disclaimer: Fire Alarm Academy is an educational course. It is not a certification, licence, or accredited program, and it is not affiliated with or endorsed by the Canadian Fire Alarm Association, ECAO, ULC Standards, or any authority having jurisdiction. Course content does not replace the CAN/ULC standards, the Canadian Electrical Code, the applicable building or fire code, manufacturer instructions, or the direction of your AHJ. Always verify against the edition adopted in your jurisdiction.

© 2026 Fire Alarm Academy. Built for the trade.