Suite fault isolator

An isolator that prevents a fault inside one dwelling unit from disabling notification in neighbouring units. Canadian AHJ guidance is specific on two points: the isolator is installed outside the suite it protects, and acceptance is demonstrated by imposing a wire-to-wire short inside each suite to prove corridor devices are unaffected.

Read more: The four Canadian fire alarm standards explained

Fire Alarm Academy

Canadian fire alarm training built on CAN/ULC standards and the Ontario codes — taught by a licensed 309A electrician who does the work.

Learn

Free Resources

Company

Disclaimer: Fire Alarm Academy is an educational course. It is not a certification, licence, or accredited program, and it is not affiliated with or endorsed by the Canadian Fire Alarm Association, ECAO, ULC Standards, or any authority having jurisdiction. Course content does not replace the CAN/ULC standards, the Canadian Electrical Code, the applicable building or fire code, manufacturer instructions, or the direction of your AHJ. Always verify against the edition adopted in your jurisdiction.