Sleeping room requirement

In residential and care occupancies, the alarm signal must reach at least 75 dBA in sleeping rooms with intervening doors closed, and must be a low-frequency signal. S524 provides empirical data showing roughly 25 dBA of loss through a closed door, which is what drives sounder placement inside dwelling units.

Read more: Who can legally work on fire alarms in Ontario

Fire Alarm Academy

Canadian fire alarm training built on CAN/ULC standards and the Ontario codes — taught by a licensed 309A electrician who does the work.

Learn

Free Resources

Company

Disclaimer: Fire Alarm Academy is an educational course. It is not a certification, licence, or accredited program, and it is not affiliated with or endorsed by the Canadian Fire Alarm Association, ECAO, ULC Standards, or any authority having jurisdiction. Course content does not replace the CAN/ULC standards, the Canadian Electrical Code, the applicable building or fire code, manufacturer instructions, or the direction of your AHJ. Always verify against the edition adopted in your jurisdiction.