Fire Alarm Work in British Columbia: Who Can Do It and What Governs It

British Columbia has no provincial law that names a qualification for working on fire alarm systems. That is the honest answer, and it is not the same answer as Ontario's. What BC has instead is three separate layers. On the electrical side, Construction Electrician is a compulsory trade under SkilledTradesBC, and the Electrical Safety Regulation limits who may perform regulated electrical work at all. On the code side, the BC Building Code 2024 and BC Fire Code 2024 set what must be installed, verified and tested. On the municipal side, individual local governments have written ASTTBC registration into their own fire by-laws — the City of Vancouver is one, and its by-law text is quotable. Outside those municipalities we found no BC statute or regulation that reserves fire alarm inspection, testing or verification to any designation.

Last updated August 2026 10 min read

Last updated: August 2026 · All BC sources below retrieved 16 August 2026

Quick answer

TaskWhich code appliesWhich standardWhich editionQualification required
Install a new systemBC Building Code 2024 (Vancouver: Building By-law 2025)CAN/ULC-S524Not verified — see belowNone named in any BC code text we could open. The electrical work itself is regulated work
Verify a new systemBC Building Code 2024 (Vancouver: Building By-law 2025)CAN/ULC-S537Not verifiedNo provincial rule found. In Vancouver, Bulletin 2020-006-BU/EL lists four acceptable categories
Annual inspection and testBC Fire Code 2024CAN/ULC-S536Not verifiedNo provincial rule found. In Vancouver, the Fire By-law requires a "service agent" — defined as an ASTTBC RFPT
Electrical installation workBC Electrical CodeCSA C22.1:24, 26th editionConstruction Electrician is a compulsory trade; Electrical Safety Regulation s. 4 limits who may perform regulated work
Sign off an electrical permitElectrical Safety RegulationB.C. Reg. 100/2004Field Safety Representative, Class A, B or C

Every row above is sourced in the sections that follow. Where we could not open the primary text, we say so rather than guessing.

There is no provincial qualification rule

This is the single most important thing to get right about BC, because it is where most writing on the subject goes wrong.

We searched the BC Fire Code 2024 adoption instrument, the Electrical Safety Regulation, and the Office of the Fire Commissioner's published bulletins. We did not find a BC provincial requirement that names a program, a certificate, or a designation for a person who inspects, tests or verifies a fire alarm system.

The Electrical Safety Regulation (B.C. Reg. 100/2004, consolidation current to 11 August 2026) does not contain the phrase "fire alarm" anywhere in its operative text. The province's fire safety codes and bulletins page lists bulletins on door hardware, fusible links, fire safety planning and combustible liquids — none on fire alarm systems or on the qualifications of people who service them.

That absence is the finding. It is not an oversight in our research; it is the state of the BC rules as published.

The BC codes, and one genuinely unusual feature

BC Building Code 2024. The province states: "The BC Building Code 2024 came into effect March 8, 2024. It applies to all projects with building permits applied for after that date." (BC Building Code 2024)

BC Fire Code 2024. Also effective 8 March 2024, adopted by Ministerial Order No. FSA 2023 1.

Here is the part worth knowing before you go looking for a book. BC does not publish a consolidated Fire Code. The province's own page says: "British Columbia will not be producing a consolidated BCFC document." To read the BC Fire Code you need two documents side by side:

  1. The National Fire Code of Canada 2020, free from the NRC Publications Archive; and
  2. The Schedule of Ministerial Order No. FSA 2023 1, the BC amendments.

(BC Fire Code)

Is the text free? Yes. The province states: "The BC Building Code, including Plumbing and Fire Codes, are available for free online." (Code resources)

One caution on the free HTML viewer at free.bcpublications.ca: when we checked it, it carried BC Building Code 2018, BC Fire Code 2018 and Vancouver Building By-law 2019 — not the current editions. The current codes are free, but as PDFs from gov.bc.ca. If you are reading the viewer, check which edition you are actually in.

Vancouver is its own jurisdiction — and this is real

This trips up people who move between Lower Mainland municipalities.

The City of Vancouver is "enabled under the Vancouver Charter to adopt by-laws to regulate the design and construction of buildings." The current edition is the 2025 Vancouver Building By-law, By-law No. 14343, effective 15 September 2025. (City of Vancouver)

So inside Vancouver, the Vancouver Building By-law is the building regulation — not the BC Building Code. Article numbering runs closely parallel, which is exactly why it is easy to cite the wrong document.

On the fire side, the Vancouver Fire By-law No. 14419 adopts the British Columbia Fire Code established under Ministerial Order No. FSA 20231 dated 24 November 2023, effective 8 March 2024, as amended by Ministerial Order No. FSA 202401 dated 5 April 2024. (By-law 14419)

Who may verify a fire alarm system in BC

There is no provincial answer. There is a Vancouver answer, and it is published.

Bulletin 2020-006-BU/EL, "Verification of Fire Alarm Systems Signals to Fire Department", issued 19 February 2020, references Vancouver Building By-law sentences 3.2.4.5.(1), 3.2.4.5.(2) and 3.2.4.7.(4), and CAN/ULC-S524, CAN/ULC-S537 and CAN/ULC-S561.

It sets out the organisations and individuals accepted to perform the verification:

A qualified person employed by a ULC listed manufacturer of a FAS (i.e. qualified persons employed by Simplex, Edwards, Honeywell, Mircom, Notifier, etc.)

A Registered Professional Engineer in BC (Electrical or Fire Protection), who is not involved in the installation of the FAS subjected to this engineer's verification.

A technologist in the electrical technology area recognized by ASTTBC who in addition has successfully completed the relevant FAS courses.

Plus a fourth category: a qualified person employed by a fire alarm service company holding provincial electrical qualifications with documented factory training.

(Bulletin 2020-006-BU/EL)

Read that carefully. The bulletin uses the phrase "a qualified person" in two of the four categories and does not define it further in the text we retrieved. Where a document says "a qualified person" without defining it, that is exactly what it says — we are not going to fill the gap for you.

Note also what this bulletin is: a City of Vancouver document. It does not govern Surrey, Kelowna or Prince George.

ASTTBC and the RFPT — what is law and what is association material

The Applied Science Technologists and Technicians of British Columbia (ASTTBC) registers Registered Fire Protection Technicians (RFPT).

ASTTBC describes the program as covering "fire alarms, fire pumps, unit emergency lighting, electrical generators, water-based fire protection systems, portable fire extinguishers, special suppression systems, commercial kitchen duct cleaning, and smoke control systems." Registration is by endorsement; the fire alarm endorsement is AL. (ASTTBC — Fire Protection)

ASTTBC was continued as a regulatory body under the Professional Governance Act in February 2021 and is subject to oversight by the Office of the Superintendent of Professional Governance. (RFPT Standard of Practice V4.0)

Being a regulatory body is not the same as holding a reserved practice. ASTTBC's own commissioned review is unusually direct on this point:

While Schedule 2 of the Act contemplates reserved practice for ASTTBC registrants subject to regulation, the Regulation does not currently establish reserved practice for ASTTBC registrants.

And on the practical position of RFPTs:

no statutory restrictions on their activities or qualifications, except in the minority of municipalities that presently require ASTTBC registration

(ASTTBC — Review of Registered Technical Specialists, 9 May 2022)

That is association material describing the association's own position. Treat it as such — but note it cuts against the association's interest, which is usually a sign it is accurate.

Where RFPT registration genuinely is law: Vancouver

We went looking for an actual municipal by-law rather than a claim about by-laws, and found one.

The Vancouver Fire By-law No. 14419, Schedule A, Article 1.4.1.2, defines:

Service agent means a Registered Fire Protection Technician (RFPT) certified by the Applied Science Technologists and Technicians of British Columbia (ASTTBC) specifically for the testing, inspection and maintenance of fire safety installations and equipment.

And Schedule B, Article 6.1.1.5:

A service agent shall test and inspect all fire suppression systems, emergency lighting systems, exit sign systems, fire alarm systems, fire pumps, emergency power systems and commercial kitchen exhaust systems.

(By-law 14419)

So in Vancouver, annual testing and inspection of a fire alarm system is by by-law reserved to an ASTTBC-registered RFPT. That is a municipal legal requirement, quotable and enforceable, and it is the clearest example we found.

The City also publishes a fire protection system pre-inspection certification page confirming the practical position: "Some zoning districts within Vancouver require fire safety and protection system equipment be inspected yearly by a certified fire protection technician." (City of Vancouver)

The "24 municipalities" claim, examined

You will see it stated everywhere that 24 BC municipalities require RFPT registration by by-law. The source of that number is ASTTBC itself:

Currently there are twenty-four (24) jurisdictions in BC that have enacted a municipal bylaw that require registration as an RFPT to inspect and test the fire and life safety systems in buildings.

(ASTTBC — Fire Protection)

We could not verify the number 24. Three problems:

  1. ASTTBC does not publish the list. There is no roster of which 24 jurisdictions.
  2. ASTTBC's own review gives a different number. The 2022 Review of Registered Technical Specialists says "approximately 20 of BC's 160 municipalities have established requirements in their fire bylaws that require RFPTs to conduct all testing of fire protection equipment and systems." Twenty-four and approximately twenty are not the same figure, and both come from ASTTBC.
  3. We located exactly one by-law text, Vancouver's, through official sources.

So: the mechanism is real and verified — a BC municipality can and does put RFPT registration into its fire by-law. The count is an association statement, not a verified fact, and ASTTBC's own documents disagree with each other about it. If you need to know whether it applies to you, ask the fire department in the municipality you are working in and ask them to point at the by-law section.

Technical Safety BC, permits and the electrical side

Technical Safety BC administers electrical safety in BC "in accordance with the Safety Standards Act and the Electrical Safety Regulation" — installation and operating permits, electrical contractor licences, and Field Safety Representative certification. (Technical Safety BC — Electrical)

We found no Technical Safety BC publication specific to fire alarm systems. What we did find is a pair of useful exclusions.

The Class C-R: Security Alarm FSR certificate (formerly Class SA) permits work on intruder and security alarm systems, and explicitly does not authorise "electrical work on fire alarm systems." (Class C-R Security Alarm)

The Class C-R: Low Energy certificate is the same: "The scope of work not included under this certificate includes electrical work on fire alarm systems, electrical work on security alarm systems, and electrical work in hazardous locations." (Class C-R Low Energy)

If you hold a low-energy or security-alarm restricted ticket in BC, it does not cover fire alarm electrical work. That is stated by the regulator, not inferred.

What the Electrical Safety Regulation actually requires

The regulation is free to read and short. Section 4 (1) limits who may perform regulated electrical work at all:

an individual must not perform regulated work in respect of electrical equipment unless the individual (a) holds an appropriate SkilledTradesBC certificate in respect of electrical work, (b) has successfully completed training recognized by a provincial safety manager, (c) is employed by an organization that utilizes training programs that are approved by a provincial safety manager…

The list continues with homeowners, manufacturers' technical representatives, and holders of certain other certificates.

Two provisions matter to anyone doing fire alarm testing:

Section 18 (1): "No permit is required if the only electrical work performed is testing."

And section 2 defines "testing" as "the evaluation and verification of electrical equipment by means of instruments and testing devices."

Section 20 adopts "the Canadian Electrical Code, Part I, Twenty-sixth Edition… Canadian Standards Association Standard C22.1:24" as the B.C. Electrical Code.

Field Safety Representative classes A, B and C are established by section 7, with scope limited by voltage and current. (Electrical Safety Regulation)

Electrician certification in BC

SkilledTradesBC is the trade certification authority. Construction Electrician is a compulsory trade. SkilledTradesBC states that workers in the listed trades "are required to be either registered with SkilledTradesBC as an apprentice or trade qualifier or certified as a journeyperson."

The compulsory list is Construction Electrician, Industrial Electrician, Powerline Technician, Steamfitter/Pipefitter, Refrigeration and Air Conditioning Mechanic, Gasfitter Class A and Class B, and Sheet Metal Worker. (SkilledTradesBC — Skilled Trades Certification)

Does the electrician certificate cover fire alarm work? We found no official BC statement either way. SkilledTradesBC does not publish a scope note addressing fire alarm systems, and the Electrical Safety Regulation does not mention fire alarms. What is verifiable is narrower and still useful: the electrical installation work on a fire alarm system is regulated electrical work, so section 4 of the Electrical Safety Regulation governs who may perform it, and a compulsory-trade certificate is the main route in.

BC vs Ontario

Ontario material below is Ontario law and is included only for comparison. It does not apply in BC.

QuestionBritish ColumbiaOntario
Does provincial law name a qualification for annual test/inspection?No provincial rule foundYes. Fire Code O. Reg. 213/07, Div. C 1.2.1.2.(1) — must have completed "a program or course acceptable to the Fire Marshal"
Does provincial law name a qualification for S537 verification?NoNo. Div. C 1.2.1.1 lists only annual tests/inspections, interconnection testing, and repairs/replacements/alterations. Verification is not among them
Can unqualified people do the work?Not addressed provinciallyYes under 1.2.1.2.(2), on-site supervision, max two supervised persons at a time
Is a named association written into provincial law?NoNo — CFAA is not named anywhere in Ontario's regulation
Municipal by-laws naming a designation?Yes — e.g. Vancouver Fire By-law 14419 requires an ASTTBC RFPTNot the mechanism used
Installation / verification standardsCAN/ULC-S524 / S537 (BCBC 3.2.4.5; VBBL 3.2.4.5)CAN/ULC-S524 / S537, Building Code 3.2.4.5
Referenced editionsNot verified2019 editions (Building Code Table 1.3.1.2; Fire Code Table 1.2.1.A designates S524-2019, S536-2019, S537-2019)
Electrician a compulsory trade?Yes — Construction Electrician, SkilledTradesBCYes
Separate building regulation for the largest city?Yes — Vancouver Building By-law under the Vancouver CharterNo

The headline difference: Ontario regulates the person provincially and BC does not. BC regulates the electrical worker provincially, and leaves the fire-protection technician question to municipalities.

More on the Ontario position: Who can legally work on fire alarms in Ontario.

What we could not verify

Listed plainly, because none of this appears as a claim above.

  • Which editions of CAN/ULC-S524, S536 and S537 the BC Building Code 2024 and BC Fire Code 2024 reference. We could not retrieve the Division B referenced-documents tables from the current codes. The only free referenced-documents table we could open was the superseded Vancouver Building By-law 2019, which listed CAN/ULC-S524-14 and CAN/ULC-S537-13. That is the 2019 by-law, now replaced by the 2025 edition, so we are not carrying those editions forward as current. If the edition year matters to your job, open the current code table yourself.
  • The list of the 24 (or approximately 20) BC municipalities whose by-laws require RFPT registration. Not published by ASTTBC, and the two ASTTBC figures conflict.
  • Any second municipal by-law text beyond Vancouver's. We do not doubt others exist; we could not open one through an official source.
  • Any BC provincial requirement, bulletin or directive naming who may perform a CAN/ULC-S537 verification. None found.
  • Any Office of the Fire Commissioner bulletin on fire alarm systems or on the qualifications of people who service them. None on the published bulletins page.
  • Any Technical Safety BC publication specific to fire alarm systems. None found.
  • An official statement on whether the electrician certificate covers fire alarm work. Neither SkilledTradesBC nor Technical Safety BC publishes one.

If you can point us at a primary source for any of these, we will correct this page.


We are not affiliated with ASTTBC, Technical Safety BC, SkilledTradesBC, the City of Vancouver, any authority having jurisdiction, or any association. We certify nobody. This page reports what published primary sources say and flags what they do not say.

Last updated: August 2026. BC sources retrieved 16 August 2026: BC Building Code 2024 and BC Fire Code 2024 pages, BC Codes resources page, Electrical Safety Regulation (consolidation current to 11 August 2026), Vancouver Building By-law page, Vancouver Fire By-law 14419, Vancouver Bulletin 2020-006-BU/EL, ASTTBC Fire Protection and RTS Review pages, ASTTBC RFPT Standard of Practice V4.0, Technical Safety BC FSR pages, SkilledTradesBC Skilled Trades Certification page.

Frequently asked questions

Do I need to be an ASTTBC RFPT to work on fire alarms in BC?

It depends entirely on the municipality. There is no BC provincial law requiring it. In the City of Vancouver, yes for annual testing and inspection: Fire By-law 14419 defines a service agent as an ASTTBC-registered RFPT and Schedule B 6.1.1.5 requires a service agent to test and inspect fire alarm systems. ASTTBC states that 24 BC jurisdictions have such a by-law, but does not publish the list, and its own 2022 review says approximately 20. Ask the fire department where you are working and ask them to point at the by-law section.

Is the claim that 24 BC municipalities require RFPT by bylaw actually true?

Unverified. The number comes from ASTTBC's own website. ASTTBC does not publish which jurisdictions they are, and ASTTBC's own commissioned 2022 Review of Registered Technical Specialists gives a different figure - approximately 20 of BC's 160 municipalities. We verified the mechanism by opening one actual by-law, Vancouver's. We could not verify the count.

Who is allowed to verify a fire alarm system in British Columbia?

We found no BC provincial rule on this. The City of Vancouver publishes one: Bulletin 2020-006-BU/EL, dated 19 February 2020, accepts a qualified person employed by a ULC listed manufacturer, a Registered Professional Engineer in BC not involved in the installation, a technologist in the electrical technology area recognized by ASTTBC who has completed the relevant fire alarm courses, or a qualified person employed by a fire alarm service company with provincial electrical qualifications and documented factory training. The bulletin does not define qualified person further. That bulletin applies in Vancouver only.

Does the BC Building Code apply in Vancouver?

No. The City of Vancouver is enabled under the Vancouver Charter to adopt its own building by-laws. The current edition is the 2025 Vancouver Building By-law, By-law No. 14343, effective 15 September 2025. The numbering runs close to the BC Building Code, which is exactly why people cite the wrong document. Vancouver's Fire By-law 14419 does adopt the BC Fire Code.

Where can I read the BC Fire Code, and is it free?

It is free, but it is not one book. British Columbia states it will not be producing a consolidated BC Fire Code document. You need the National Fire Code of Canada 2020, free from the NRC Publications Archive, read together with the Schedule of Ministerial Order No. FSA 2023 1, which carries the BC amendments. Both are linked in the sources. Note that the free HTML viewer at free.bcpublications.ca carried only 2018 and 2019 editions when we checked.

Does my BC electrician certificate cover fire alarm work?

There is no official BC statement either way, and we are not going to invent one. What is verifiable: Construction Electrician is a compulsory trade under SkilledTradesBC, the electrical installation work on a fire alarm system is regulated electrical work under the Electrical Safety Regulation section 4, and Technical Safety BC states that the restricted Class C-R Security Alarm and Class C-R Low Energy certificates specifically do not cover electrical work on fire alarm systems.

Sources

Related guides

Fire Alarm Academy

Canadian fire alarm training built on CAN/ULC standards and the Ontario codes — taught by a licensed 309A electrician who does the work.

Learn

Free Resources

Company

Disclaimer: Fire Alarm Academy is an educational course. It is not a certification, licence, or accredited program, and it is not affiliated with or endorsed by the Canadian Fire Alarm Association, ECAO, ULC Standards, or any authority having jurisdiction. Course content does not replace the CAN/ULC standards, the Canadian Electrical Code, the applicable building or fire code, manufacturer instructions, or the direction of your AHJ. Always verify against the edition adopted in your jurisdiction.