Powering a Fire Alarm System: What CEC Section 32 Requires

Fire alarm circuits in Canada are governed by Section 32 of the Canadian Electrical Code, and they are held to a stricter standard than ordinary low-voltage control wiring. The panel gets its own dedicated circuit with a permanently marked, red disconnect that locks in the ON position. Conductors are copper, rated at least 300 V, and must be kept independent of all other wiring. And because a fire alarm is a safety control device, its circuits are treated as Class 1 regardless of voltage or power limitation.

Last updated September 2026 7 min read

Sources checked August 2026

Quick answer

  • Section 32 covers local fire alarm systems, permanently connected smoke and CO alarms, and fire pumps
  • It is supplementary: it amends the general rules rather than replacing them
  • Dedicated circuit, with a permanently marked RED disconnect lockable in the ON position
  • Copper conductors, minimum 300 V insulation rating
  • Independent of all other wiring: no sharing a raceway with lighting or power
  • Class 1 treatment regardless of voltage, because it is a safety control circuit
  • In Ontario: the 2024 OESC (29th edition), in force 1 May 2025

Why this is stricter than you might expect

A fire alarm circuit runs at 24 volts. It draws very little current. Every instinct built from ordinary control wiring says: treat it as low voltage, Class 2, and get on with it.

That instinct is wrong in Canada, and there is a specific rule that makes it wrong.

Rule 16-010 (commonly cited) requires that circuits to safety control devices, where failure would introduce a direct fire or life hazard, be treated as Class 1 circuits regardless of voltage or power limitation. (IAEI Magazine, Canadian column)

A fire alarm system is exactly that kind of device. So the Class 2 allowances a technician might expect (the relaxed separation rules, the lighter wiring methods) do not apply.

If you have come from American practice, this is one of the sharper divergences. It is not that Canada is fussier for its own sake; the Canadian code makes the reasoning explicit and then applies it consistently.

What Section 32 covers

Section 32 applies to local fire alarm systems, permanently connected smoke and carbon monoxide alarms, and fire pumps. It is a supplementary section, meaning it amends the general rules of the code rather than standing alone. (Electrical Industry News Week)

The requirements

A note on rule numbers. The requirements below are well attested across Canadian sources. Several of the rule numbers come from secondary guides whose CEC edition is not stated. Treat the requirement as solid and verify the number against your own copy of the OESC before citing it in a compliance document.

Conductors: commonly cited as Rule 32-100

RequirementDetail
MaterialCopper
AmpacityAdequate for the circuit
Insulation ratingMinimum 300 V
Minimum sizeNo. 16 AWG where pulled · No. 19 AWG where laid
AlternativeOptical fibre permitted

Note the 300 V insulation rating. Ordinary Class 2 control cable is frequently rated lower. Using it on a fire alarm circuit is a common and entirely avoidable failure.

Wiring method: commonly cited as Rule 32-102

Permitted methods:

  • Totally enclosed metal raceway
  • Metal-armoured or metal-sheathed cable
  • Rigid non-metallic conduit
  • Electrical non-metallic tubing (ENT): but in combustible construction, ENT requires embedment in at least 50 mm of masonry or concrete

The theme is mechanical protection. A fire alarm circuit has to survive the building around it, including, up to a point, the early stages of a fire.

Separation: commonly cited as Rule 32-102(3)

This one produces more field arguments than any other.

Fire alarm conductors must be kept independent of all other wiring, except at defined connection points: the supply, signals, ancillary devices, and communication circuits.

In practice: no sharing a raceway with lighting or power circuits. Not "keep them apart where convenient." Independent.

Where a shared pathway is genuinely unavoidable, that is an AHJ conversation before you pull, not after.

Bonding: commonly cited as Rule 32-104

Exposed non-current-carrying metal parts bonded to ground per Section 10, with a bonding conductor incorporated where the system uses non-metallic wiring methods.

The dedicated circuit and the red lock-on: commonly cited as Rule 32-108

This is the requirement everyone knows and the rule number we are least sure about.

The fire alarm panel must be supplied by a separate, dedicated circuit, with a disconnecting means that is:

  • Permanently marked
  • RED
  • Lockable in the ON position

The reasoning is obvious once you have seen the failure. A fire alarm panel sharing a circuit with anything else can be de-energised by someone troubleshooting that other thing. Red marking makes the breaker identifiable at a glance. The lock-on makes killing it a deliberate act rather than a casual one.

On site, the failure modes are predictable: the breaker is on a shared circuit because the panel arrived after the panel schedule was finalised; the lock-on device was never fitted; or it was fitted and later removed during a renovation and nobody put it back. All three are visible on inspection.

Dwelling unit smoke and CO alarms: Rule 32-200 ✅ verified

Confirmed directly from an Alberta Municipal Affairs interpretation bulletin:

  • Conductors copper, with ampacity adequate for the circuit, therefore #14 AWG or larger in practice
  • Interconnection permitted as an approved Class 2 method in combustible buildings
  • Low-voltage control cable must not enter enclosures containing higher-voltage conductors

(Alberta STANDATA 18-CECI-32)

Rule 32-304 (fire pump service boxes) is confirmed from the same bulletin.

One more Canadian requirement worth knowing

Nova Scotia's electrical safety bulletin makes two points that are easy to miss:

  1. All fire alarm systems (code-required or voluntary) must be wired per CAN/ULC-S524 and CEC Section 32.
  2. Dwelling unit smoke alarms must not be supplied from GFCI- or AFCI-protected circuits.

(Nova Scotia Electrical Safety Bulletin 03-02)

Caveat on that source: the bulletin dates from 2006 and cites S524-01, and directs readers to consult the Chief Electrical Inspector for current guidance. The principle (that voluntary installations are held to the same standard) is consistent with S524's own scope, which explicitly covers both required and voluntary installations.

Which code edition applies in Ontario

The 2024 Ontario Electrical Safety Code (the 29th edition) came into force 1 May 2025. Electrical work performed after that date must meet it. The OESC comprises the Canadian Electrical Code Part I plus Ontario-specific amendments. (Electrical Safety Authority)

Two codes, one installation

A fire alarm install is governed by two separate documents at once, and they cover different things:

CAN/ULC-S524CEC Section 32
GovernsHow the system is designed and installedHow the electrical side is executed
CoversCircuit classes, supervision, fault tolerance, device placement, zoning, isolatorsConductors, wiring methods, separation, bonding, the dedicated circuit and disconnect
Comes fromULC (published by ULSE), referenced by the Building Code for new construction and by the Ontario Fire Code (Art. 6.3.1.8) for repairs, replacements and alterationsCSA C22.1, adopted provincially as the OESC
Enforced byBuilding official / fire AHJElectrical inspector

You can satisfy one and fail the other. A system wired to perfect S524 architecture, sharing a raceway with the lighting circuit, fails. A beautifully executed dedicated circuit feeding a panel with no fault tolerance across zones fails too.

Two inspectors, two documents, two sign-offs.

Field checklist

  • Panel on a dedicated circuit: nothing else on it
  • Disconnect permanently marked, red, lockable in the ON position: and the lock-on actually installed
  • Conductors copper, 300 V minimum insulation
  • Minimum #16 AWG pulled / #19 AWG laid
  • Wiring method: enclosed metal raceway, metal-armoured/sheathed cable, rigid non-metallic conduit, or ENT, with the 50 mm masonry embedment rule if ENT in combustible construction
  • Fire alarm conductors independent of all other wiring
  • Bonding per Section 10
  • Dwelling unit smoke alarms not on GFCI or AFCI protection
  • Working to the edition in force in your jurisdiction

Fire Alarm Academy provides educational content only. It does not confer any certification, licence or credential, and it is not affiliated with, endorsed by, or accredited by the Canadian Fire Alarm Association, the Electrical Contractors Association of Ontario, ULC Standards, UL Standards and Engagement, CSA Group, the Electrical Safety Authority, any authority having jurisdiction, or any manufacturer. Always work from the edition of any standard adopted by your authority having jurisdiction.

Frequently asked questions

Does a fire alarm panel need its own circuit in Canada?

Yes. Section 32 requires a separate dedicated circuit with a permanently marked, red disconnecting means that is lockable in the ON position.

Why does the fire alarm breaker have to be red?

So it is identifiable at a glance and nobody de-energises the panel by accident. The lock-on requirement makes shutting it off a deliberate act.

Can fire alarm wiring share a conduit with lighting circuits?

No. Fire alarm conductors must be kept independent of all other wiring except at defined connection points. If a shared pathway seems unavoidable, that is a conversation with the AHJ before you pull.

Is fire alarm wiring Class 1 or Class 2 in Canada?

Class 1. Rule 16-010 requires circuits to safety control devices (where failure introduces a direct fire or life hazard) to be treated as Class 1 regardless of voltage or power limitation.

What size conductors does a fire alarm circuit need?

Copper, with ampacity adequate for the circuit, minimum 300 V insulation rating, and not smaller than No. 16 AWG where pulled or No. 19 AWG where laid. Optical fibre is permitted as an alternative.

Does Section 32 apply to a fire alarm system the code did not require?

Yes. Voluntary installations are held to the same standard, CAN/ULC-S524 scope covers both required and voluntary systems.

Which edition of the electrical code applies in Ontario?

The 2024 Ontario Electrical Safety Code, 29th edition, in force 1 May 2025. It is the Canadian Electrical Code Part I plus Ontario amendments.

Can dwelling unit smoke alarms be on an AFCI circuit?

Nova Scotia electrical safety bulletin says no, smoke alarms must not be supplied from GFCI- or AFCI-protected circuits. Confirm the current position with your provincial authority, as that bulletin is dated.

Sources

Related guides

CAN/ULC-S524, S537, S536 and S1001: What Each Standard Actually Covers

Canada splits fire alarm work across four separate standards where the American system uses one. S524 governs installation. S537 governs verification, a one-time event that proves the install matches the design. S536 governs periodic inspection and testing, forever after. S1001 governs integrated testing, where the fire alarm has to talk to other building systems. Confusing verification with inspection is the most expensive mistake in Canadian fire alarm work, and it happens constantly.

Fire Alarm Work for Licensed Electricians: Where to Start

You already know how to install the system. What is usually missing is which document governs the task, which edition of it your province actually adopted, and whether the law names a qualification for the person doing it. Take those in order. First: S524 installs, S537 verifies, S536 inspects and tests, S1001 tests the integrations, and the code doing the requiring flips from the Building Code for new work to the Fire Code for a system in service. Second: the edition is the one your code's table designates, which is almost never the newest published. Third: Ontario names a qualification for annual inspection, interconnection testing, and repairs and alterations, and names none at all for verification. Everything technical sits downstream of those three answers.

Every Canadian Fire Alarm Code and Standard: And Where to Get Each One Free

Some of it is free, some of it costs money, and one of Ontario's two codes is no longer published in full at all. The Ontario Fire Code is free and complete on e-Laws. The Ontario Building Code is free but now runs one page; it adopts the National Building Code of Canada 2020, which is itself free from the NRC, plus an Ontario Amendment Document you have to email for. The CAN/ULC standards are not free and there is no legitimate free copy of any of them. This page lists every document, what it costs, where to get it, and which version is actually in force.

Which Fire Alarm Standard Applies to What I'm Doing? (Ontario)

Five common tasks, five different answers. Installing a new system is CAN/ULC-S524 under Building Code Article 3.2.4.5.(1). Verifying it is CAN/ULC-S537 under Article 3.2.4.5.(2), a Building Code duty, not a Fire Code one. Annual inspection and testing of a system already in service is CAN/ULC-S536 under Fire Code Article 6.3.2.2. Repairing, replacing or altering a component on an existing system goes back to S524, this time under Fire Code Article 6.3.1.8. Testing interconnections to other fire protection and life safety systems is CAN/ULC-S1001 under Fire Code Article 6.10.1.1, but only if the system was installed on or after 1 January 2020 and the Building Code required it to be verified to S1001. Ontario names a qualification requirement for three of those five tasks. It names none at all for verification.

Fire Alarm Academy

Canadian fire alarm training built on CAN/ULC standards and the Ontario codes, taught by a licensed 309A electrician who does the work.

Learn

Free Resources

Company

Disclaimer: Fire Alarm Academy is an educational course. It is not a certification, licence, or accredited program, and it is not affiliated with or endorsed by the Canadian Fire Alarm Association, ECAO, ULC Standards, or any authority having jurisdiction. Course content does not replace the CAN/ULC standards, the Canadian Electrical Code, the applicable building or fire code, manufacturer instructions, or the direction of your AHJ. Always verify against the edition adopted in your jurisdiction.

© 2026 Fire Alarm Academy. Built for the trade.